Limitor®- PD Back-up Fuses
without Controlled , for German standard VDE 0670 T402
DIN HV BACK-UP FUSES FOR TRANSFORMERS
10 / 24 kV, length 442mm
current
In
Clearing I2t
at
Voltage
Breaking
capacity
I1
Minimum
breaking
current I3 = Imin
Cold resistance
R20 (+/-10%)
?56mm
45DB240V6,3PD F1000252 6 3 A 0 8 kA2s 63 kA 23 A 640 m? 32 W 1 2 4 kg
45DB240V10PD G1000253 10 A 2 kA2s 63 kA 36 A 386 m? 48 W 1 2 4 kg
45DB240V16PD H1000254 16 A 2 34 kA2s 63 kA 73 A 127 m? 43 W 1 2 4 kg
45DB240V20PD J1000255 20 A 3 9 kA2s 63 kA 91 A 97 m? 53 W 1 2 4 kg
45DB240V25PD K1000256 25 A 6 5 kA2s 63 kA 116 A 74 m? 64 W 1 2 4 kg
45DB240V32PD L1000257 31 5 A 7 kA2s 63 kA 125 A 61 m? 85 W 1 2 4 kg
45DB240V40PD M1000258 40 A 14 2 kA2s 63 kA 161 A 43 m? 103 W 1 2 4 kg
?65mm
45DB240V50PD N1000259 50 A 24 2 kA2s 63 kA 230 A 35 m? 146 W 1 3 1 kg
45DB240V63PD P1000260 63 A 46 4 kA2s 63 kA 350 A 25 m? 163 W 1 3 1 kg
45DB240V80PD Q1000261 80 A 104 kA2s 63 kA 460 A 19 m? 196 W 1 3 1 kg
?88mm
45DB240V100PD R1000262 100 A 140 kA2s 63 kA 420 A 14 m? 279 W 1 4 3 kg
45DB240V6,3PD
45DB240V80PD
6 / 12 kV, length 292mm
Clearing I2t
at
Voltage
Breaking
capacity I1
Minimum
breaking
current I3