Protection class Housing: IP 40 (DIN 40050) Power supply 12-24 VDC +10/-15% Power consumption 3 W max. Mounting Snap on DIN-rail mountable by Phoenix UMK modul Load cell input Max. four 350 O load cells Excitation voltage: 2.5 VAC 425 Hz Excitation current: max. 60 mA Input gain range for F.S.: 0-0.17 mV/V up to 0-3.3 mV/V Dead load compensation: 80 % of max. input Max. cable length: appr. 150 m Environmental conditions Temperature range: -10 to +40°C Dimensions in mm: 113 + 77 + 37 (W + D + H) Weight: appr. 0.2 kg Warm up time: 30 minutes Optional dual setpoint unit MP 20/10 Two FORM-C reed relays Up to eight setpoints can be arranged with four units | Relay coil voltage: 12-24 VDC Relay coil current: < 25 mA Optional power supply unit MP 20/20 110/230 VAC Optional load cell junction unit MP 20/30 up to four 350 O load cells connectable Analogue output Voltage output (Vout): +/- 10 VDC at min 500 O Current loop output (Iout): 0/4-20 mA at max. 500 O Deviation between Vout and Iout: 3% of F.S. Accuracy Linearity: < 0.005 % F.S. at 23°C Temperature effect on zero: < 0.003%/K Temperature effect on span: < 0.0015%/K Max. deviation 0-F.S.: < 50 ppm Signal filter: active low pass filter in 64 steps from 0.25-32 Hz Drift 5 min. upon power on: < 20 ppm of F.S. |