Product type designation
|
|
|
|
|
Input current
|
|
|
|
|
from backplane bus 5 V DC, max.
|
120 mA
|
120 mA
|
140 mA
|
140 mA
|
Power loss
|
|
|
|
|
Power loss, typ.
|
1.5 W
|
1.5 W
|
2.5 W
|
2.5 W
|
Digital outputs
|
|
|
|
|
Number of digital outputs
|
8
|
8
|
16
|
16
|
|
1
|
1
|
1
|
1
|
short-circuit protection
|
No; to be provided externally
|
No; to be provided externally
|
No; to be provided externally
|
No; to be provided externally
|
Switching capacity of the outputs
|
|
|
|
|
|
0.5 A
|
0.5 A
|
0.5 A
|
0.5 A
|
|
5 W
|
5 W
|
5 W
|
5 W
|
Output voltage
|
|
|
|
|
|
24 V
|
24 V
|
24 V
|
24 V
|
|
0.1 V; with 10 kOhm load
|
0.1 V; with 10 kOhm load
|
0.1 V; with 10 kOhm load
|
0.1 V; with 10 kOhm load
|
Output current
|
|
|
|
|
|
0.5 A
|
0.5 A
|
0.5 A
|
0.5 A
|
|
10 µA
|
10 µA
|
10 µA
|
10 µA
|
Output delay with resistive load
|
|
|
|
|
|
50 µs
|
50 µs
|
50 µs
|
50 µs
|
|
200 µs
|
200 µs
|
200 µs
|
200 µs
|
Total current of the outputs (per group)
|
|
|
|
|
horizontal installation
|
|
|
|
|
|
4 A; Current per mass
|
4 A; Current per mass
|
8 A; Current per mass
|
8 A; Current per mass
|
Relay outputs
|
|
|
|
|
Switching capacity of contacts
|
|
|
|
|
|
0.5 A
|
0.5 A
|
0.5 A
|
0.5 A
|
|
5 W
|
5 W
|
5 W
|
5 W
|
|
0.5 A
|
0.5 A
|
0.5 A
|
0.5 A
|
Cable length
|
|
|
|
|
|
500 m
|
500 m
|
500 m
|
500 m
|
|
150 m
|
150 m
|
150 m
|
150 m
|
Interrupts/diagnostics/status information
|
|
|
|
|
Alarms
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Diagnostic messages
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Diagnostics indication LED
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Yes
|
Yes
|
Yes
|
Yes
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Potential separation digital outputs
|
|
|
|
|
|
1
|
1
|
1
|
1
|
|
500 V AC
|
500 V AC
|
500 V AC
|
500 V AC
|
Degree and class of protection
|
|
|
|
|
Degree of protection acc. to EN 60529
|
|
|
|
|
|
Yes
|
Yes
|
Yes
|
Yes
|
Standards, approvals, certificates
|
|
|
|
|
CE mark
|
Yes
|
Yes
|
Yes
|
Yes
|
Ambient conditions
|
|
|
|
|
Free fall
|
|
|
|
|
|
0.3 m; five times, in dispatch package
|
0.3 m; five times, in dispatch package
|
0.3 m; five times, in dispatch package
|
0.3 m; five times, in dispatch package
|
Ambient temperature during operation
|
|
|
|
|
|
-40 °C; = Tmin; startup @ -25 °C
|
-20 °C; = Tmin; startup @ 0 °C
|
-40 °C; = Tmin; startup @ -25 °C
|
-20 °C; = Tmin; startup @ 0 °C
|
|
70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 4 (no adjacent points) for horizontal mounting position
|
60 °C; = Tmax
|
70 °C; = Tmax; Tmax > +60 °C number of simultaneously activated outputs 8 (no adjacent points) for horizontal mounting position
|
60 °C; = Tmax
|
Ambient temperature during storage/transportation
|
|
|
|
|
|
-40 °C
|
-40 °C
|
-40 °C
|
-40 °C
|
|
70 °C
|
70 °C
|
70 °C
|
70 °C
|
Extended ambient conditions
|
|
|
|
|
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
|
Tmin ... Tmax at 1080 hPa ... 795 hPa (-1000 m ... +2000 m) // Tmin ... (Tmax - 10K) at 795 hPa ... 658 hPa (+2000 m ... +3500 m) // Tmin ... (Tmax - 20K) at 658 hPa ... 540 hPa (+3500 m ... +5000 m)
|
Relative humidity
|
|
|
|
|
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
100 %; RH incl. condensation/frost (no commissioning under condensation conditions)
|
Resistance
|
|
|
|
|
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3B2 mold, fungus and dry rot spores (with the exception of fauna). The supplied connector covers must remain on the unused interfaces during operation!
|
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3C4 (RH < 75%) incl. salt spray according to EN 60068-2-52 (degree of severity 3). The supplied connector covers must remain on the unused interfaces during operation!
|
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|
Yes; Class 3S4 incl. sand, dust. The supplied connector covers must remain on the unused interfaces during operation!
|