Technical data
|
EK9300
|
Task within EtherCAT system
|
coupling of standard digital and analog EtherCAT Terminals and EtherCAT Box modules to PROFINET RT networks
|
Number of EtherCAT Terminals
|
depending on the process data size
|
Type/number of peripheral signals
|
depending on the process data size
|
Protocol
|
PROFINET RT
|
Data transfer rates
|
10/100 Mbaud
|
Configuration
|
not required
|
Bus interface
|
2 x RJ45 (switched)
|
Power supply
|
24 V DC (-15 %/+20 %)
|
Input current
|
typ. 120 mA + (total E-bus current)/4
|
Current consumption E-bus
|
up to 2 A
|
Power contacts
|
24 V DC max./10 A max.
|
Electrical isolation
|
500 V (power contact/supply voltage/Ethernet)
|
Dimensions (W x H x D)
|
65 mm x 100 mm x 80 mm
|
Operating/storage temperature
|
0…+55 °C/-25…+85 °C
|
Relative humidity
|
95 %, no condensation
|
Vibration/shock resistance
|
conforms to EN 60068-2-6/EN 60068-2-27
|
EMC immunity/emission
|
conforms to EN 61000-6-2/EN 61000-6-4
|
Protect. class/installation pos.
|
IP 20/variable
|
Approvals
|
CE, Ex
|