General specifications |
Signal type |
Digital Input |
Supply |
Connection |
Power Rail or terminals 9+, 10- |
Rated voltage |
19 ... 30 V DC |
Ripple |
≤ 10 % |
Rated current |
≤ 30 mA |
Power loss |
≤ 600 mW |
Power consumption |
≤ 600 mW |
Input |
Connection |
terminals 1+, 2-; 3+, 4- |
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current |
approx. 10 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I ≥ 6.5 mA |
Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
Output |
Connection |
terminals 5, 6; 7, 8 |
Output I |
signal ; relay |
Output II |
signal ; relay |
Contact loading |
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 30 V DC/2 A resistive load |
Minimum switch current |
2 mA / 24 V DC |
Energized/De-energized delay |
≤ 20 ms / ≤ 20 ms |
Mechanical life |
107 switching cycles |
Transfer characteristics |
Switching frequency |
≤ 10 Hz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21 |
Protection degree |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 100 g |
Dimensions |
12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 in) , housing type A2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
BASEEFA 06 ATEX 0092 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I |
Statement of conformity |
PF 06 CERT 0972 X |
|
Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 Gc |
Output I, II |
|
|
Contact loading |
50 V AC/2 A/cos φ > 0.7; 30 V DC/2 A resistive load |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 , EN 61241-11:2006 |
International approvals |
FM approval |
|
|
Control drawing |
16-533FM-12 (cFMus) |
UL approval |
|
|
Control drawing |
16-533FM-12 (cULus) |
IECEx approval |
IECEx BAS 06.0025 |
|
Approved for |
[Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |