产品阐述 |
24 V DC |
General specifications |
Signal type |
Digital Input |
Supply |
Connection |
terminals 23+, 24- or power feed module/Power Rail |
Rated voltage |
20 ... 30 V DC |
Rated current |
approx. 130 mA |
Power loss |
2.2 W |
Power consumption |
2.5 W |
Input |
Connection |
input I: terminals 1+, 3-
input II: terminals 4+, 6-
input III: terminals 13+, 14- (control input 1)
input IV: terminals 15+, 14- (control input 2) |
Input I, II |
2-wire sensor, sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
|
Open circuit voltage/short-circuit current |
8.2 V / 10 mA |
|
Pulse duration |
min. 250 µs , overlap on direction of rotation signal: ≥ 125 µs |
|
Input frequency |
rotation direction monitoring 0.001 ... 1000 Hz slip monitoring 10 ... 1000 Hz |
|
Lead monitoring |
breakage I ≤ 0.15 mA; short-circuit I > 4 mA |
Input III, IV |
|
|
Active/Passive |
I > 4 mA (for min. 100 ms) / I < 1.5 mA |
|
Open circuit voltage/short-circuit current |
18 V / 5 mA |
Output |
Connection |
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 19+, 20-
output IV: terminals 21+, 20-
output V: terminals 7-, 8+ |
Output I, II |
signal, relay |
|
Contact loading |
250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
|
Mechanical life |
5 x 107 switching cycles |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Output III and IV |
signal , electronic output, passive |
|
Contact loading |
40 V DC |
|
Signal level |
1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof)
0-signal: blocked output (off-state current ≤ 10 µA) |
Output V |
analog |
|
Current range |
0 ... 20 mA or 4 ... 20 mA |
|
Open loop voltage |
max. 24 V DC |
|
Load |
max. 650 Ω |
|
Fault signal |
downscale I ≤ 3.6 mA, upscale I ≥ 21.5 mA (acc. NAMUR NE43) |
Programming interface |
|
|
Connection |
programming socket |
|
Interface |
RS 232 |
Collective error message |
Power Rail |
Transfer characteristics |
Input I and II |
|
|
Measurement range |
0.001 ... 1000 Hz |
|
Resolution |
slip monitoring: 1% frequency measurement: 0,1% of measured value; but >0.001Hz |
|
Accuracy |
slip monitoring: 1% frequency measurement: 0.5% of measured value; but >0.001Hz |
|
Measuring time |
frequency measurement: < 100 ms |
|
Influence of ambient temperature |
0.003 %/K (30 ppm) |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
300 g |
Dimensions |
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |