General specifications |
Signal type |
Analog output |
Supply |
Rated voltage |
loop powered |
Power loss |
0.2 W |
Field circuit |
Connection |
terminals 1+, 2 / 3- |
Voltage |
≥ 16 V for supply voltage > 21 V |
Current |
4 ... 20 mA (linear transmission 1 ... 22 mA) |
Load |
≤ 800 Ω (at 20 mA) |
Supply circuit |
Connection |
terminals 8-, 9+ |
Voltage |
max. 30 V DC |
Current |
4 ... 20 mA (quiescent current < 0.5 mA) |
Power loss |
150 mW at 20 mA and UE < 24 V |
Transfer characteristics |
Voltage drop |
see note |
Influence of ambient temperature |
< 0.5 µA/K |
Damping |
approx. 3 dB |
Rise time |
≤ 20 µs at 0 Ω, ≤ 600 µs with 800 Ω load |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electrical isolation |
IEC 62103 |
Electromagnetic compatibility |
NE 21 |
Protection degree |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 120 g |
Dimensions |
20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
PTB 02 ATEX 2064 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (2)G [EEx ib] IIC |
Statement of conformity |
PF 11 CERT 0902 X |
|
Group, category, type of protection, temperature class |
II 3G Ex nA IIC T4 Gc |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2005 |
International approvals |
FM approval |
device with FM approval on request |