General specifications |
Signal type |
Analog output |
Supply |
Rated voltage |
loop powered |
Control circuit |
Connection |
terminals 12-, 11+; 8-, 10-, 9+ |
Voltage |
5 ... 35 V DC |
Current |
4 ... 20 mA |
Power loss |
at 20 mA and Uin < 24.3 V: < 250 mW per channel
at 20 mA and Uin > 24.3 V: < 500 mW per channel |
Field circuit |
Connection |
terminals 1+, 2-; 4+, 5- |
Voltage |
for 5V < Uin < 24.3V: ≥ 0.9 x Uin - (0.37 x current in mA) - 1.0
for Uin > 24.3 V: ≥ 21 V - (0.36 x current in mA) |
Short-circuit current |
at Uin > 24.3 V : ≤ 65 mA |
Transfer current |
≤ 40 mA |
Transfer characteristics |
Rise time |
≤ 5 ms at bounce from 4 ... 20 mA and Uin < 24 V |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 100 g |
Dimensions |
20 x 107 x 115 mm (0.8 x 4.2 x 4.5 in) , housing type B1 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
BAS 98 ATEX 7343 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C ≤ Tamb ≤ 60 °C) |
Statement of conformity |
TÜV 99 ATEX 1499 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA II T4 [device in zone 2] |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 |
International approvals |
FM approval |
|
|
Control drawing |
116-0129 |
UL approval |
|
|
Control drawing |
116-0173 (cULus) |
IECEx approval |
IECEx BAS 05.0004 |
|
Approved for |
[Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I |