产品阐述 |
Current output 0/4 mA ... 20 mA |
General specifications |
Signal type |
Analog input |
Supply |
Connection |
terminals 14+, 15- or power feed module/Power Rail |
Rated voltage |
20 ... 30 V DC |
Ripple |
within the supply tolerance |
Power loss/power consumption |
≤ 0.98 W / 0.98 W |
Input |
Connection |
terminals 1, 2, 3, 4 |
RTD |
type Pt10, Pt50, Pt100, Pt500, Pt1000 (EN 60751: 1995)
type Pt10GOST, Pt50GOST, Pt100GOST, Pt500GOST, Pt1000GOST (6651-94)
type Cu10, Cu50, Cu100 (P50353-92)
type Ni100 (DIN 43760) |
|
Measuring current |
approx. 200 µA with RTD |
|
Types of measuring |
2-, 3-, 4-wire connection |
|
Lead resistance |
max. 50 Ω per lead |
|
Measuring circuit monitoring |
sensor breakage, sensor short-circuit |
Thermocouples |
type B, E, J, K, N, R, S, T (IEC 584-1: 1995)
type L (DIN 43710: 1985)
type TXK, TXKH, TXA (P8.585-2001) |
|
Cold junction compensation |
external and internal |
|
Measuring circuit monitoring |
sensor breakage |
Voltage |
selectable within the range -100 ... 100 mV |
Potentiometer |
0 ... 20 kΩ (2-wire connection), 0.8 ... 20 kΩ (3-wire connection) |
Input resistance |
≥ 1 MΩ (-100 ... 100 mV) |
Output |
Connection |
output I: terminal 7: source (-), sink (+), terminal 8: source (+), terminal 9: sink(-) |
Output |
Analog current output |
|
Current range |
0 ... 20 mA or 4 ... 20 mA |
|
Fault signal |
downscale 0 or 2 mA, upscale 21.5 mA (acc. NAMUR NE43) |
|
Source |
load 0 ... 550 Ω
open-circuit voltage ≤ 18 V |
|
Sink |
Voltage across terminals 5 ... 30 V. If the current is supplied from a source > 16.5 V,
series resistance of ≥ (V - 16.5)/0.0215 Ω is needed, where V is the source voltage.
The maximum value of the resistance is (V - 5)/0.0215 Ω. |
Transfer characteristics |
Reaction time |
worst case value (sensor breakage and/or sensor short circuit detection enabled)
mV: 1 s, thermocouples with CJC: 1.1 s, thermocouples with fixed reference temperature: 1.1 s, 3- or 4-wire RTD: 920 ms, 2-wire RTD: 800 ms, Potentiometer: 2.05 s |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Insulation coordination |
UL 61010-1 |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 130 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
CESI 04 ATEX 143 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD, I (M1), [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
Statement of conformity |
TÜV 02 ATEX 1797 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA II T4 [device in zone 2] |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2006, EN 60079-11:2007, EN 60079-15:2005, EN 60079-26:2007, EN 61241-0:2006, EN 61241-11:2006 |
International approvals |
UL approval |
|
|
Control drawing |
116-0316 |
CSA approval |
|
|
Control drawing |
366-024CS-12 (cCSAus) |
IECEx approval |
IECEx TUN 07.0003 |
|
Approved for |
[Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I |