General specifications |
Signal type |
Digital Output |
Supply |
Power loss |
0.8 W |
Input |
Connection |
terminals 7, 8, 9 |
Input current |
≤ 21 mA per channel |
Output |
Safety note |
Attention! Combination of output Ex i with output not Ex i is notpermitted.
If load voltage > 50 V, de-energize before removing the terminals. |
Connection |
terminals 1, 2, 3; 4, 5, 6 |
Contact loading |
230 V AC/2 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Energized/De-energized delay |
approx. 10 ms / approx. 5 ms |
Mechanical life |
5 x 106 switching cycles |
Transfer characteristics |
Switching frequency |
< 10 Hz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 65 °C (-4 ... 149 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 100 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
DMT 00 ATEX E 016 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD [Ex ia] IIC , [Ex iaD] |
Statement of conformity |
TÜV 00 ATEX 1621 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0: 2009 , EN 60079-11:2007 , EN 60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006 |
International approvals |
CSA approval |
|
|
Control drawing |
116-0156 |