General specifications |
Signal type |
Digital Output |
Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
20 ... 30 V DC |
Power consumption |
max. 3.3 W at 45 mA output current |
Input |
Connection |
terminals 7, 8, 9 |
Input current |
approx. 3 mA at 24 V DC |
Signal level |
1-signal: 16 ... 30 V DC
0-signal: 0 ... 5 V DC |
Output |
Connection |
channel 1: terminals 1+, 2-, 3
channel 2: terminals 4+, 5-, 6- |
Internal resistor |
272 Ω |
Current |
≤ 45 mA |
Voltage |
≥ 11.7 V |
Open loop voltage |
min. 24 V |
Output signal |
These values are valid for the rated operating voltages from 20 ... 30 V DC. |
Energized/De-energized delay |
≤ 20 ms / ≤ 20 ms |
Line fault detection |
signal at short-circuit RB < 50 Ω, lead breakage RB > 10 kΩ , test current < 650 µA |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 50 °C (-4 ... 122 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
ZELM 00 ATEX 0024 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD [Ex ia] IIC; [Ex iaD] [circuit(s) in zone 0/1/2/20/21/22] |
Statement of conformity |
TÜV 02 ATEX 1820 X |
|
Group, category, type of protection, temperature class |
II 3G Ex nA II T4 |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007 , EN 60079-15:2010 |
International approvals |
FM approval |
|
|
Control drawing |
16-548FM-12 |
IECEx approval |
IECEx TUN 04.0001 |
|
Approved for |
[Ex ia] IIC , [Ex iaD] |