产品阐述 |
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
General specifications |
Signal type |
Digital Input |
Supply |
Connection |
terminals 23, 24 |
Rated voltage |
20 ... 90 V DC / 48 ... 253 V AC 50 ... 60 Hz |
Power loss/power consumption |
≤ 2 W ; 2.5 VA / 2.2 W ; 3 VA |
Input |
Connection |
Input I: intrinsically safe: terminals 1+, 3-
Input II: non-intrinsically safe: terminals 13+, 14- |
Input I |
sensor acc. to EN 60947-5-6 (NAMUR) or mechanical contact |
|
Pulse duration |
> 50 µs |
|
Input frequency |
0.001 ... 5000 Hz |
|
Lead monitoring |
breakage I ≤ 0.15 mA; short-circuit I > 6.5 mA |
Input II |
startup override: 1 ... 1000 s, adjustable in steps of 1 s |
|
Active/Passive |
I > 4 mA (for min. 100 ms) / I < 1.5 mA |
|
Open circuit voltage/short-circuit current |
18 V / 5 mA |
Output |
Connection |
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
outout III: terminasl 19+, 20-
output IV: terminals 8+, 7- |
Output I, II |
signal, relay |
|
Contact loading |
250 V AC / 2 A / cos φ ≥ 0.7 ; 40 V DC / 2 A |
|
Mechanical life |
5 x 107 switching cycles |
|
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Output III |
electronic output, passive |
|
Contact loading |
40 V DC |
|
Signal level |
1-signal: (L+) - 2.5 V (50 mA, short-circuit/overload proof)
0-signal: switched off (off-state current ≤ 10 µA) |
Output IV |
analog |
|
Current range |
0 ... 20 mA or 4 ... 20 mA |
|
Open loop voltage |
max. 24 V DC |
|
Load |
max. 650 Ω |
|
Fault signal |
downscale I ≤ 3.6 mA , upscale ≥ 21.5 mA (acc. NAMUR NE43) |
Transfer characteristics |
Output IV |
|
|
Resolution |
< 10 µA |
|
Accuracy |
< 20 µA |
|
Influence of ambient temperature |
0.005 %/K (50 ppm) |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
300 g |
Dimensions |
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
TÜV 99 ATEX 1471 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C ≤ Tamb ≤ 60 °C) |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007, EN 60079-26:2007 , EN 61241-11:2006 |
International approvals |
FM approval |
|
|
Control drawing |
16-538FM-12 |