General specifications |
Signal type |
Analog input |
Supply |
Connection |
Power Rail or terminals 23+, 24- |
Rated voltage |
20 ... 30 V DC |
Rated current |
approx. 130 mA |
Power loss |
2 W |
Power consumption |
2.5 W |
Input |
Connection |
terminals 1, 2, 3 |
Input I |
|
|
Input signal |
0/4 ... 20 mA |
|
Available voltage |
≥ 15 V at 20 mA |
|
Open circuit voltage/short-circuit current |
24 V / 33 mA |
|
Input resistance |
45 Ω (terminals 2, 3) |
|
Lead monitoring |
breakage I < 0.2 mA; short-circuit I > 22 mA |
Output |
Connection |
output I: terminals 10, 11, 12
output II: terminals 16, 17, 18
output III: terminals 8+, 7- |
Output signal |
0 ... 20 mA or 4 ... 20 mA |
Output I, II |
signal, relay |
|
Contact loading |
250 V AC / 2 A / cos φ ≥ 0.7 ; 40 DC / 2 A |
|
Mechanical life |
5 x 107 switching cycles |
Output III |
Signal, analog |
|
Current range |
0 ... 20 mA or 4 ... 20 mA |
|
Open loop voltage |
max. 24 V DC |
|
Load |
max. 650 Ω |
|
Fault signal |
downscale I ≤ 3.6 mA, upscale I ≥ 21 mA (acc. NAMUR NE43) |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
300 g |
Dimensions |
40 x 119 x 115 mm (1.6 x 4.7 x 4.5 in) , housing type C3 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
TÜV 01 ATEX 1701 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1) G [Ex ia] IIC
II (1) D [Ex iaD] |
Statement of conformity |
TÜV 02 ATEX 1885 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 |
Output I, II |
|
|
Contact loading |
50 V AC/2 A/cos φ > 0.7; 40 V DC/1 A resistive load |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007, EN60079-15:2005 , EN 60079-26:2007 , EN 61241-11:2006 |
International approvals |
FM approval |
|
|
Control drawing |
16-554FM-12 (cFMus) |