产品阐述 |
24 V DC |
General specifications |
Signal type |
Digital Input |
Supply |
Connection |
Power Rail or terminals 22+, 23+, 24- |
Rated voltage |
20 ... 35 V DC |
Ripple |
≤ 10 % |
Rated current |
≤ 130 mA |
Power loss |
2.1 W |
Power consumption |
max. 2.3 W |
Input |
Connection |
terminals 10+, 12- |
Open circuit voltage/short-circuit current |
approx. 8.4 V DC / approx. 11.7 mA |
Lead resistance |
≤ 50 Ω, in hazardous area cable capacitances and inductivities are to be taken into account |
Switching point |
|
|
Relay de-energized |
I < 2.1 mA and I > 5.9 mA |
|
Relay energized |
2.8 mA < I < 5.3 mA |
Response delay |
≤ 1 ms |
Output |
Connection |
output I: terminals 13, 14 ; output II: terminals 15, 21 ; output III: terminals 16+, 17- |
Output I |
signal , safety oriented ; relay |
Output I, II |
|
|
Contact loading |
50 V AC/1 A/cos φ > 0.7; 24 V DC/1 A resistive load |
|
Mechanical life |
50 x 106 switching cycles |
Output II |
signal , not safety oriented ; relay |
Output III |
fault signal , not safety oriented ; electronic output, passive |
|
Rated voltage |
10 ... 30 V DC |
|
Signal level |
1-signal: (L+) -2.5 V (7 mA, short-circuit proof) / 0-signal: blocked output
(Leakage current ≤ 10 mA) |
Transfer characteristics |
Switching frequency |
5 Hz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21 |
Protection degree |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 280 g |
Dimensions |
40 x 107 x 115 mm (1.6 x 4.2 x 4.5 in) , housing type C1 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
PTB 00 ATEX 2042 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD [EEx ia] IIC [circuit(s) in zone 0/1/2] |
Statement of conformity |
TÜV 99 ATEX 1493 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 |
Directive conformity |
|
|
Directive 94/9/EC |
EN 50014, EN 50020 , EN 60079-0:2006, EN 60079-15:2005 |
International approvals |
FM approval |
|
|
Control drawing |
116-0158 |