产品阐述 |
Input 0/4 mA ... 20 mA
2 x Output 0/4 mA ... 20 mA
(current sink) |
General specifications |
Signal type |
Analog input |
Supply |
Connection |
Power Rail or terminals 14+, 15- |
Rated voltage |
20 ... 35 V DC |
Ripple |
within the supply tolerance |
Power loss |
1.6 W |
Power consumption |
2.5 W |
Input |
Connection |
terminals 1+, 2-, 3 or 5-, 6+ |
Input signal |
0/4 ... 20 mA |
Voltage drop |
≤ 2.4 V at 20 mA (terminals 5, 6) |
Input resistance |
≤ 76 Ω terminals 2-, 3 ; ≤ 500 Ω terminals 1+, 3 (250 Ω load) |
Available voltage |
≥ 16 V at 20 mA terminals 1+, 3 |
Output |
Connection |
terminals 7+, 8-; 10+, 11- |
Output signal |
0/4 ... 20 mA (overload > 25 mA) |
Ripple |
max. 50 µA rms |
External supply (loop) |
11 ... 30 V DC |
Transfer characteristics |
Deviation |
at 20 °C (68 °F), 0/4 ... 20 mA
≤ 10 µA incl. calibration, linearity, hysteresis, loads and fluctuations of supply voltage |
Frequency range |
field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 7.5 kHz (-3 dB)
control side into the field side: bandwidth with 0.5 Vpp signal 0.3 ... 7.5 kHz (-3 dB) |
Settling time |
200 µs |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 200 g |
Dimensions |
20 x 124 x 115 mm (0.8 x 4.9 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
BAS 99 ATEX 7060 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD, [Ex ia] IIC, [Ex iaD] (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
EC-Type Examination Certificate |
DMT 01 ATEX E 133 |
|
Group, category, type of protection |
I (M1) [Ex ia] I |
Statement of conformity |
TÜV 99 ATEX 1499 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA II T4 [device in zone 2] |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2006, EN 60079-11:2007, EN 61241-11:2006 , EN 60079-15:2005 , EN 50303:2000 |
International approvals |
UL approval |
|
|
Control drawing |
116-0173 (cULus) |
General information |
Note |
Both output loads must be connected to ensure complete and correct operation within the technical specification. |