产品阐述 |
redundant supply |
Supply |
Connection |
terminals 11+, 12-
terminals 8+, 9- |
Rated voltage |
20 ... 30 V DC
The maximum rated operating voltage of the devices plugged onto the Power Rail must not be exceeded. |
Power loss |
≤ 2.4 W |
Output |
Power Rail feed |
Output current: max. 4 A |
Fault signal |
relay output: NO contact |
Contact loading |
30 V AC/ 2 A / cos φ ≥ 0.7 ; 40 V DC/ 2 A |
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Fusing |
5 AT |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-25 ... 60 °C (-13 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 100 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
Statement of conformity |
TÜV 00 ATEX 1618 X |
|
Group, category, type of protection, temperature class |
II 3G Ex nA nC IIC T4 |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009 , EN 60079-15:2010 |
International approvals |
FM approval |
|
|
Control drawing |
116-0160 |
|
Approved for |
Class I, Division 2, Groups A, B, C, D; Class I, Zone 2, IIC |
CSA approval |
|
|
Control drawing |
116-0160 |
|
Approved for |