General specifications |
Signal type |
Digital Input |
Supply |
Connection |
terminals 14, 15 |
Rated voltage |
207 ... 253 V AC |
Power loss |
1 W |
Power consumption |
max. 1.5 W |
Input |
Connection |
terminals 1+, 2+, 3-; 4+, 5+, 6- |
Rated values |
acc. to EN 60947-5-6 (NAMUR), see system descrtption for electrical data |
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Output |
Connection |
output I: terminals 7, 8 ; output II: terminals 8, 9 |
Signal level |
1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current
0-signal: switched off (off-state current ≤ 10 µA) |
Output I, II |
signal ; electronic output, passive |
Transfer characteristics |
Switching frequency |
≤ 5 kHz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 50178:1997 |
Conformity |
Electromagnetic compatibility |
NE 21 |
Protection degree |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
PTB 98 ATEX 2164 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1) G [Ex ia] IIC
II (1) D [Ex iaD] |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0: 2006, EN 60079-11: 2007 |
International approvals |
UL approval |
|
|
Control drawing |
116-0145 |
CSA approval |
|
|
Control drawing |
116-0047 |