General specifications |
Signal type |
Digital Input |
Supply |
Connection |
terminals 14, 15 |
Rated voltage |
103.5 ... 126 V AC , 45 ... 65 Hz |
Power consumption |
1 W |
Input |
Connection |
terminals 1+, 2+, 3- |
Rated values |
acc. to EN 60947-5-6 (NAMUR) |
Open circuit voltage/short-circuit current |
approx. 8 V DC / approx. 8 mA |
Switching point/switching hysteresis |
1.2 ... 2.1 mA / approx. 0.2 mA |
Line fault detection |
breakage I ≤ 0.1 mA , short-circuit I > 6 mA |
Pulse/Pause ratio |
min. 20 ms / min. 20 ms |
Output |
Connection |
terminals 7, 8, 9 |
Output |
signal, relay |
Contact loading |
253 V AC/2 A/cos φ > 0.7; 126.5 V AC/4 A/cos φ > 0.7; 40 V DC/2 A resistive load |
Energized/De-energized delay |
approx. 20 ms / approx. 20 ms |
Mechanical life |
107 switching cycles |
Transfer characteristics |
Switching frequency |
< 10 Hz |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Low voltage |
|
|
Directive 2006/95/EC |
EN 61010-1:2010 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529:2001 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 150 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
PTB 00 ATEX 2081 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1) G [Ex ia] IIC, II (1) D [Ex ia] IIIC |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2007 , EN 61241-11:2006 |
International approvals |
FM approval |
|
|
Control drawing |
116-0035 |
UL approval |
|
|
Control drawing |
116-0145 |
CSA approval |
|
|
Control drawing |
116-0047 |
IECEx approval |
IECEx PTB 11.0031 |
|
Approved for |
[Ex ia] IIC , [Ex ia] IIIC , [Ex ia] I |