General specifications |
Signal type |
Analog input |
Supply |
Connection |
Power Rail or terminals 11+, 12- |
Rated voltage |
19 ... 30 V DC |
Ripple |
within the supply tolerance |
Power loss |
≤ 1.4 W |
Power consumption |
≤ 1.7 W |
Input |
Connection |
terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -) |
Input resistance |
10 kΩ terminals 4 (common), 6-/2- |
Output rated operating current |
terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V
terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V
terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F) |
Transmission range |
0 ... -20 V |
Output |
Connection |
terminals 7-, 8+ |
Load |
≥ 9 kΩ (3-wire sensor), ≥ 2 kΩ (2-wire sensor) |
Voltage |
0 ... -20 V |
Output resistance |
24 Ω typ., 27 Ω maximum
Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer. |
Transfer characteristics |
Deviation |
DC transfer error (with 10 kΩ load) < 10mV |
Bandwidth |
-0.1 dB at 10 kHz; -1 dB at 20 kHz |
Time delay relative to input |
7.1 ±0.3 µs |
Ripple |
in 200 kHz bandwidth < 20 mVrms
in 20 kHz bandwidth < 3 mVrms |
Directive conformity |
Electromagnetic compatibility |
|
|
Directive 2004/108/EC |
EN 61326-1:2006 |
Conformity |
Electromagnetic compatibility |
NE 21:2006 |
Protection degree |
IEC 60529 |
Ambient conditions |
Ambient temperature |
-20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications |
Protection degree |
IP20 |
Mass |
approx. 125 g |
Dimensions |
20 x 119 x 115 mm (0.8 x 4.7 x 4.5 in) , housing type B2 |
Mounting |
on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with Ex-areas |
EC-Type Examination Certificate |
BAS 02 ATEX 7206 , for additional certificates see www.pepperl-fuchs.com |
|
Group, category, type of protection |
II (1)GD, [Ex ia] IIC, [Ex iaD], (-20 °C ≤ Tamb ≤ 60 °C) [circuit(s) in zone 0/1/2] |
EC-Type Examination Certificate |
DMT 01 ATEX E 133 |
|
Group, category, type of protection |
I (M1) [Ex ia] I |
Statement of conformity |
TÜV 99 ATEX 1499 X , observe statement of conformity |
|
Group, category, type of protection, temperature class |
II 3G Ex nA II T4 [device in zone 2] |
Directive conformity |
|
|
Directive 94/9/EC |
EN 60079-0:2009, EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 |
International approvals |
UL approval |
|
|
Control drawing |
116-0316 (cULus) |
IECEx approval |
IECEx BAS 05.0078
IECEx BAS 10.0085X |
|
Approved for |
[Zone 0] [Ex ia] IIC, [Ex iaD], [Ex ia] I
Ex nA II T4 |