General specifications |
Switching element function |
AC NO |
Rated operating distance |
15 mm |
Installation |
quasi flush |
Output polarity |
AC |
Assured operating distance |
0 ... 12.15 mm |
Reduction factor rAl |
0.33 |
Reduction factor rCu |
0.28 |
Reduction factor r304 |
0.81 |
Nominal ratings |
Operating voltage |
20 ... 253 V |
Switching frequency |
0 ... 20 Hz |
Hysteresis |
typ. 5 % |
Reverse polarity protection |
reverse polarity tolerant |
Voltage drop |
< 5 V (IL > 50 mA); < 8 V (IL < 50 mA) |
Momentary current
(20 ms, 0.1 Hz) |
0 ... 1600 mA |
Operating current |
5 ... 200 mA |
Off-state current |
0 ... 1.7 mA |
Operating voltage display |
LED, green |
Switching state indication |
LED, yellow |
Approvals and certificates |
UL approval |
cULus Listed, General Purpose |
CSA approval |
cCSAus Listed, General Purpose |
CCC approval |
Certified by China Compulsory Certification (CCC) |
Ambient conditions |
Ambient temperature |
-25 ... 70 °C (-13 ... 158 °F) |
Mechanical specifications |
Connection type |
cable PVC , 2 m |
Core cross-section |
0.75 mm2 |
Housing material |
brass, nickel-plated |
Sensing face |
PBT |
Housing diameter |
30 mm |
Protection degree |
IP67 |
Note |
1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V
Safety fuse ≤ 0.3 A (quick-blow) according to IEC 60127-2 Sheet 1
Recommendation: after a short circuit, check that the device is functioning correctly. |